The technological process of converting the feedstock (fuel) into the final product (electricity) is reflected in the technological schemes of power plants.

Process flow diagram of a coal-fired TPP is shown in Figure 3.4. It is a complex complex of interconnected paths and systems: a dust preparation system; fuel supply and fuel ignition system (fuel path); ash removal system; gas-air tract; a steam-water path system, including a steam-water boiler and a turbine unit; system for preparation and supply of additional water to replenish feed water losses; technical water supply system for steam cooling; system of network water heating installations; electric power system, including a synchronous generator, step-up transformer, high-voltage switchgear, etc.

Below is a brief description of the main systems and paths of the technological scheme of a TPP using the example of a coal-fired TPP.

Rice. 3.3. Process flow diagram of a pulverized coal power plant

1. Dust preparation system. Fuel path... Solid fuel delivery is carried out by rail in special open wagons 1 (see fig. 3.4). Gondola cars with coal are weighed on railway scales. In winter, gondola cars with coal are passed through a defrosting hothouse, in which the gondola car walls are heated with heated air. Next, the gondola car is pushed into an unloading device - a car dumper 2 , in which it rotates around the longitudinal axis at an angle of about 180 0; the coal is discharged onto the grates overlapping the receiving bunkers. Coal from bunkers is fed by feeders to a conveyor 4 , through which it enters either the coal warehouse 3 , or through the crushing department 5 in the raw coal bunker boiler room 6 , which can also be delivered from a coal warehouse.

From the crushing plant, the fuel enters the raw coal bunker 6 , and from there through the feeders to the pulverized coal mills 7 ... Coal dust is pneumatically conveyed through a separator 8 and cyclone 9 into the coal dust bin 10 , and from there feeders 11 supplied to the burners. The air from the cyclone is sucked in by the mill fan 12 and is fed into the boiler combustion chamber 13 .

This entire fuel path, together with the coal storage, belongs to the fuel supply system, which is maintained by the personnel of the fuel and transport department of the TPP.

Pulverized coal boilers must also have a starting fuel, usually fuel oil. Fuel oil is delivered in railway tanks, in which it is heated by steam before being discharged. With the help of the first and second lift pumps, it is supplied to the oil injectors. The starting fuel can also be natural gas coming from the gas pipeline through the gas control point to the gas burners.

At TPPs that burn gas and oil fuel, the fuel economy is significantly simplified in comparison with pulverized coal TPPs. The coal storage, the crushing department, the conveyor system, the raw coal and dust bunker, as well as the ash collection and ash removal systems are becoming unnecessary.

2... Air-gas path. Slag ash removal system. The air required for combustion is supplied to the air duct.

blower steam boiler heaters 14 ... Air is usually taken from the upper part of the boiler room and (with steam boilers of high capacity) from the outside of the boiler room.

The gases formed during combustion in the combustion chamber, after leaving it, pass sequentially through the gas ducts of the boiler plant, where in the superheater (primary and secondary, if a cycle with intermediate superheating of steam is carried out) and the water economizer give heat to the working fluid, and the air heater - supplied to the steam boiler air. Then in ash collectors (electrostatic precipitators) 15 gases are cleaned from fly ash and through the chimney 17 smoke exhausters 16 released into the atmosphere.

Slag and ash falling out under the combustion chamber, air heater and ash collectors are washed off with water and fed through channels to dredging pumps 33 , which pump them into ash dumps.

3... Steam-water tract. Steam superheated in a superheater from a steam boiler 13 through steam lines and a nozzle system to the turbine 22 .

Condensate from condenser 23 turbines are supplied by condensate pumps 24 through regenerative low pressure heaters 18 into the deaerator 20 , in which the water is brought to a boil; at the same time, it is freed from the aggressive gases O 2 and CO 2 dissolved in it, which prevents corrosion in the steam-water path. From the deaerator, water is supplied by feed pumps 21 through high pressure heaters 19 into the boiler economizer, providing preheating of water and significantly increasing the efficiency of the TPP.

The steam-water path of the TPP is the most complex and responsible, since this path has the highest metal temperatures and the highest steam and water pressures.

To ensure the functioning of the steam-water tract, a system for the preparation and supply of additional water to replenish the losses of the working fluid is required, as well as a system of technical water supply of the TPP to supply cooling water to the turbine condenser.

4... Additional water preparation and supply system. Additional water is obtained as a result of chemical purification of raw water, carried out in special ion-exchange filters for chemical water purification.

Steam and condensate losses due to leaks in the steam-water path are replenished in this scheme with chemically demineralized water, which is supplied from the demineralized water tank by a transfer pump to the condensate line behind the turbine condenser.

Devices for chemical treatment of make-up water are located in the chemical workshop 28 (chemical water treatment shop).

5... Steam cooling system. Cooling water is supplied to the condenser from the water supply receiving well 26 circulation pumps 25 ... The cooling water heated in the condenser is discharged into the collection well 27 the same source of water at a certain distance from the place of intake, sufficient so that the heated water does not mix with the intake.

In many technological schemes of thermal power plants, cooling water is pumped through the condenser tubes by circulation pumps. 25 and then enters the cooling tower (cooling tower), where, due to evaporation, the water is cooled by the same temperature difference by which it was heated in the condenser. The water supply system with cooling towers is mainly used at CHP plants. IES uses a water supply system with cooling ponds. With evaporative cooling of water, the vapor is approximately equal to the amount of steam condensing in the turbine condensers. Therefore, replenishment of the water supply systems is required, usually with water from the river.

6. System of networked water heating installations. The schemes may include a small network heating unit for heating the power plant and the adjacent village. To network heaters 29 In this unit, steam comes from the turbine extractions, condensate is removed through the line 31 ... Mains water is supplied to the heater and removed from it through pipelines 30 .

7. Electrical power system. An electric generator rotated by a steam turbine generates an alternating electric current, which goes through a step-up transformer to the busbars of the open switchgear (OSG) of the TPP. Busbars of the auxiliary system are also connected to the generator terminals through an auxiliary transformer. Thus, the consumers of the auxiliary needs of the power unit (electric motors of auxiliary units - pumps, fans, mills, etc.) are powered by the generator of the power unit. To supply electric power to electric motors, lighting devices and devices of the power plant, there is an electrical switchgear for auxiliary needs 32 .

In special cases (emergency situations, load shedding, start-up and shutdowns), auxiliary power supply is provided through the standby switchgear bus transformer. Reliable power supply of electric motors of auxiliary units ensures the reliability of operation of power units and TPPs as a whole. Interruption of power supply for own needs leads to failures and accidents.

The fundamental difference between the technological scheme of a gas turbine power plant (GTU) and a steam turbine one is that in a GTU the chemical energy of the fuel is converted into mechanical energy in one unit - a gas turbine, as a result of which there is no need for a steam boiler.

The gas turbine unit (Fig. 3.5) consists of a combustion chamber, a gas turbine GT, an air compressor K and an electric generator G. Compressor K sucks in atmospheric air, compresses it to an average of 6-10 kg / cm 2 and supplies it to the combustion chamber of the combustor. Fuel (for example, diesel oil, natural or industrial gas) also gets into the combustion chamber and is burned in compressed air.


Rice. 3.4. Simplified process flow diagram of a gas turbine

power plants on liquid or gas fuel: T - fuel; V -

air; КС - combustion chamber; GT - gas turbine; K - air compressor; G - electric generator
Hot gases with a temperature of 600–800 ° С from the combustion chamber enter the GT gas turbine. Passing through the turbine, they expand to atmospheric pressure and, moving at high speed between the blades, rotate the turbine shaft. Exhaust gases are discharged through the exhaust pipe into the atmosphere. A significant portion of the power of a gas turbine is expended in rotating the compressor and other auxiliary devices.

The main advantages of gas turbine units in comparison with steam turbine units are:

1) lack of a boiler plant and chemical water treatment;

2) significantly less demand for cooling water, which makes it possible to use GTU in areas with limited water resources;

3) significantly fewer operating personnel;

4) quick start-up;

5) lower cost of generated electricity.
3.1.3. Layout diagrams of TPP
TPPs by type (structure) of the thermal scheme are subdivided into block and non-block.

With a block scheme All the main and auxiliary equipment of the plant has no technological connections with the equipment of another plant of the power plant. In fossil fuel power plants, steam is supplied to each turbine only from one or two connected boilers. A steam turbine plant, the turbine of which is powered by steam from one steam boiler, is called monoblock, in the presence of two boilers for one turbine - double-block.

With a non-block diagram TPP steam from all steam boilers enters a common mainline and only from there is distributed to individual turbines. In some cases, it is possible to direct steam directly from steam boilers to turbines, however, the common connecting line is preserved, so you can always use steam from all boilers to power any turbine. The lines carrying water to the steam boilers (feed lines) are also cross-linked.

Block TPPs are cheaper than non-block ones, since the pipeline diagram is simplified and the number of fittings is reduced. It is easier to control individual units at such a station, block-type installations are easier to automate. In operation, the work of one block does not affect the neighboring blocks. When expanding the power plant, the subsequent unit can have a different capacity and operate at new parameters. This makes it possible to install more powerful equipment with higher parameters at the expandable station, i.e. allows to improve the equipment and improve the technical and economic indicators of the power plant. At the same time, the processes of setting up new equipment do not affect the operation of previously installed units. However, for normal operation of block TPPs, the reliability of their equipment should be much higher than that of non-block ones. There are no standby steam boilers in the units; if the possible productivity of the boiler is higher than the flow rate required for a given turbine, part of the steam (the so-called hidden reserve, which is widely used at non-block TPPs) cannot be transferred here to another unit. For steam turbine plants with intermediate superheating of steam, the block scheme is practically the only possible one, since the non-block scheme of the station in this case will turn out to be overly complicated.

In our country, steam turbine units of TPPs without controlled extraction of steam with an initial pressure P 0 ≤8.8 MPa and installations with controlled extractions at P 0 ≤12.7 MPa, operating in cycles without intermediate superheating of steam, are built non-block. At higher pressures (at KES at P 0 ≥12.7 MPa, and at CHPP at P 0 = 23.5 MPa) all steam turbine units operate in cycles with reheating, and stations with such installations are built in modular units.

The main building (main building) houses the main and auxiliary equipment directly used in the technological process of the power plant. The mutual arrangement of equipment and building structures is called the layout of the main building of the power plant.

The main building of a power plant usually consists of a turbine room, a boiler room (with a bunker room for solid fuel operation) or a reactor room at a nuclear power plant and a deaerator room. In the engine room, along with the main equipment (primarily turbine units), there are: condensate pumps, regenerative low and high pressure heaters, feed pumping units, evaporators, steam converters, network heaters (at CHP), auxiliary heaters and other heat exchangers.

In a warm climate (for example, in the Caucasus, Central Asia, etc.), in the absence of significant atmospheric precipitation, dust storms, etc. at IES, especially gas and oil, open equipment is used. At the same time, sheds are arranged over the boilers, the turbine units are protected with light shelters; the auxiliary equipment of the turbine unit is placed in a closed condensation room. The specific cubic capacity of the main building of the IES with an open layout is reduced to 0.2–0.3 m 3 / kW, which makes the construction of the IES cheaper. Overhead cranes and other lifting mechanisms are installed in the premises of the power plant for the installation and repair of power equipment.

In fig. 3.6. the layout diagram of the power unit of the pulverized-coal power plant is shown: I - room for steam generators; II - machine room, III - cooling water pumping station; 1 - unloading device; 2 - crushing plant; 3 - water economizer and air heater; 4 - steam superheaters; 5 , 6 - combustion chamber; 7 - pulverized coal burners; 8 –The steam generator; 9 - mill fan; 10 - bunker of coal dust; 11 - dust feeders; 12 - pipelines for reheat steam; 13 - deaerator; 14 - steam turbine; 15 - electric generator; 16 - a step-up electrical transformer; 17 - capacitor; 18 - supply and drain pipelines of cooling water; 19 - condensate pumps; 20 - regenerative HDPE; 21 - feed pump; 22 - regenerative LDPE; 23 - blower fan; 24 - ash collector; 25 - slag and ash channels; EE- high voltage electricity.

In fig. 3.7 shows a simplified layout diagram of a gas-oil power plant with a capacity of 2400 MW, indicating the location of only the main and part of the auxiliary equipment, as well as the dimensions of the structures (m): 1 - boiler room; 2 –Turbine department; 3 - condenser compartment; 4 - generator compartment; 5 - deaerator department; 6 - blower fan; 7 - regenerative air heaters; 8 - auxiliary switchgear (RUSN); 9 - chimney.

Rice. 3.7. Layout of the main building of the gas-oil

power plants with a capacity of 2400 MW
The main equipment of the IES (boiler and turbine units) is located in the main building, boilers and a pulverized plant (at IESs that burn, for example, coal in the form of dust) - in the boiler room, turbine units and their auxiliary equipment - in the turbine room of the power plant. At the IES, mainly one boiler is installed per turbine. The boiler with the turbine unit and their auxiliary equipment form a separate part - the monoblock of the power plant.

For turbines with a capacity of 150–1200 MW, boilers with a capacity of 500–3600 m 3 / h of steam, respectively, are required. Previously, the state district power station used two boilers per turbine, i.e. double-blocks . At the IES without intermediate superheating of steam with turbine units with a capacity of 100 MW or less, a non-block centralized scheme was used, in which steam from the boilers is diverted into a common steam line, and from it is distributed between the turbines.

The dimensions of the main building depend on the capacity of the equipment placed in it: the length of one block is 30–100 m, the width is 70–100 m. The height of the turbine hall is about 30 m, the boiler room is 50 m more. The efficiency of the layout of the main building is estimated approximately by the specific cubic capacity, which is about 0.7-0.8 m 3 / kW at a pulverized coal power plant. , and at the gas-oil plant - about 0.6–0.7 m 3 / kW. Part of the auxiliary equipment of the boiler room (smoke exhausters, blowing fans, ash collectors, dust cyclones and dust separators of the dust preparation system) are often installed outside the building, in the open air.

IES is built directly at water supply sources (river, lake, sea); often a reservoir (pond) is created next to the IES. On the territory of the IES, in addition to the main building, structures and devices for technical water supply and chemical water treatment, fuel facilities, electrical transformers, switchgears, laboratories and workshops, material warehouses, office premises for personnel serving the IES are located. Fuel is usually delivered to the IES territory by train. Ash and slag from the combustion chamber and ash collectors are removed hydraulically. On the territory of the IES, railways and highways are laid, conclusions are being built power lines, engineering ground and underground communications. The area of ​​the territory occupied by the IES facilities is, depending on the power plant capacity, fuel type and other conditions, 25–70 hectares .

Large-scale pulverized coal-fired power plants in Russia are serviced by personnel at the rate of 1 person for every 3 MW of capacity (approximately 1000 people at IES with a capacity of 3,000 MW); in addition, maintenance personnel are required.

The capacity of the IES depends on water and fuel resources, as well as the requirements of environmental protection: ensuring the normal cleanliness of the air and water basins. Emissions with fuel combustion products in the form of solid particles into the air in the area of ​​the IES operation are limited by the installation of perfect ash collectors (electrostatic precipitators with an efficiency of about 99%). The remaining impurities, oxides of sulfur and nitrogen, are dispersed by means of high chimneys, which are built to remove harmful impurities into the higher layers of the atmosphere. Chimneys up to 300 m or more in height are constructed of reinforced concrete or with 3-4 metal trunks inside a reinforced concrete shell or a common metal frame.

Controlling a wide variety of IES equipment is possible only on the basis of comprehensive automation of production processes. Modern condensing turbines are fully automated. The boiler unit has automated control over the processes of fuel combustion, supplying the boiler unit with water, maintaining the temperature of steam overheating, etc. Other processes of the IES are also automated: maintaining the specified operating modes, starting and stopping units, protecting equipment in case of abnormal and emergency conditions.
3.1.4. The main equipment of TPP
To the main equipment of TPP include steam boilers (steam generators), turbines, synchronous generators, transformers.

All listed units are standardized according to the relevant indicators. The choice of equipment is primarily determined by the type of power plant and its capacity. Almost all newly designed power plants are modular, their main characteristic is the power of the turbine units.

At present, serial domestic condensing power units of thermal power plants with a capacity of 200, 300, 500, 800 and 1200 MW are being produced. For the CHPP, along with units with a capacity of 250 MW, turbine units with a capacity of 50, 100 and 175 MW are used, in which the block principle is combined with individual equipment cross-links.

For a given power plant capacity, the range of equipment included in the power units is selected according to its capacity, steam parameters and the type of fuel used.
3.1.4.1. Steam boilers
Steam boiler(PC) heat exchanger for generating steam with a pressure exceeding atmospheric pressure, forming together with auxiliary equipment boiler unit.

The characteristics of the PC are:


  • steam production;

  • steam operating parameters (temperature and pressure) after the primary and reheaters;

  • heating surface, i.e. the surface, on the one hand, washed by flue gases, and on the other - by feed water;

  • Efficiency, i.e. the ratio of the amount of heat contained in the steam to the calorific value of the fuel consumed to produce this steam.
The steam flow rate for the turbine is usually set for the winter operation of the power plant. The capacity of the steam boiler should be selected taking into account the increase in steam consumption to the turbine due to the increase in pressure in the condenser in the summer season, steam and condensate leaks, the inclusion of network installations for heat supply and other costs. In accordance with this, the productivity of the steam boiler is selected according to the maximum flow of fresh steam through the turbine, taking into account the steam consumption for the auxiliary needs of the power plant and providing a certain margin for using the rotating reserve and other purposes.

Weight, dimensions, metal consumption and available equipment for mechanization and automation of service are also characteristic of the PC.

The first PCs were spherical. The PC built in 1765 by I. Polzunov, who created the first universal steam engine and thus laid the foundation for the energy use of water vapor, also had such a shape. At first, PCs were made from copper, then from cast iron. At the end of the 18th century, the level of development of ferrous metallurgy made it possible to make steel cylindrical PCs from sheet material by riveting. Gradual changes in PC designs have led to numerous variations. The cylindrical boiler, which had a diameter of up to 0.9 m and a length of 12 m, was mounted using brick lining, in which all the gas channels were laid out. The heating surface of such a PC was formed only in the lower part of the boiler.

The desire to increase the parameters of the PC led to an increase in the size and an increase in the number of flows of water and steam. The increase in the number of threads went in two directions: development gas-tube boilers, in particular, locomotive gas-tube steam boilers, and the development water tube boilers, which are the basis of modern boiler units. An increase in the heating surface of water-tube boilers was accompanied by an increase in the dimensions and, first of all, in the height of the PC. PC efficiency reached 93–95%.

Originally, water tube PCs were PCs only bar aban type in which bundles of straight or curved pipes (coils) were combined with cylindrical steel drums (Fig. 3.8).

Rice. 3.8. Schematic diagram of a drum-type PC:

1 - combustion chamber; 2 - burner; 3 - screen pipes; 4 -drum;

5 - downpipes; 6 - superheater; 7 - secondary (intermediate) superheater; 8 - economizer; 9 - air heater.
In the combustion chamber 1 the burners are located 2, through which a mixture of fuel with heated air enters the furnace. The number and type of burners depend on their performance, unit power and type of fuel. The three most common fuels are coal, natural gas and fuel oil. The coal is preliminarily converted into coal dust, which is blown into the furnace with the help of air through the burners.

The walls of the combustion chamber are covered with pipes from the inside (screens) 3, which absorb heat from hot gases. Water enters the screen pipes through unheated down pipes 5 out of the drum 4, in which the given level is constantly maintained . In the wall tubes, water boils and moves upward in the form of a steam-water mixture, then getting into the steam space of the drum. Thus, during the operation of the boiler, there is a natural circulation of water with steam in the circuit: drum - downpipes - screen pipes - drum. Therefore, the boiler shown in fig. 3.8 is called a natural circulation drum boiler. The steam outlet to the turbine is replenished by supplying feed water to the boiler drum using pumps.

The steam supplied from the wall tubes to the steam space of the drum is saturated and in this form, although it has a full working pressure, is not yet suitable for use in a turbine, since it has a relatively small operability. In addition, the moisture content of saturated steam during expansion in the turbine increases to the limits that are dangerous for the reliability of the rotor blades. Therefore, steam is sent from the drum to the superheater 6, where an additional amount of heat is given to it, due to which it becomes superheated from saturated. At the same time, its temperature rises to about 560 ° C and, accordingly, its performance increases. Depending on the location of the superheater in the boiler and, consequently, on the type of heat exchange carried out in it, there are radiation, screen (semi-radiation) and convective superheaters.

Radiant superheaters placed on the ceiling of the combustion chamber or on its walls, often between the pipes of the screens. They, like the evaporative screens, perceive the heat emitted by the torch of the combusted fuel. Screen steam superheaters, made in the form of separate flat screens of pipes connected in parallel, are reinforced at the outlet from the furnace in front of the convective part of the boiler. Heat exchange in them is carried out both by radiation and convection. Convective superheaters located in the boiler unit flue, usually behind screens or behind the firebox; they are multi-row coil packs. Superheaters consisting only of convective stages are usually installed in medium and low pressure boilers at a superheated steam temperature not exceeding 440–510 ºС. In high-pressure boilers with significant steam superheating, combined superheaters are used, including convective, screen, and sometimes radiation parts.

At a steam pressure of 14 MPa (140 kgf / cm 2) and above, a secondary (intermediate) superheater is usually installed behind the primary superheater 7 ... It, like the primary one, is formed of steel pipes bent into coils. Steam is sent here, which has been exhausted in the high-pressure cylinder (HPC) of the turbine and has a temperature close to the saturation temperature at a pressure of 2.5-4 MPa. . In the secondary (intermediate) superheater, the temperature of this steam rises again to 560 ° C, and its efficiency increases accordingly, after which it passes through a medium-pressure cylinder (MPC) and a low-pressure cylinder (LPC), where it expands to the exhaust steam pressure (0.003-0.007 MPa ). The use of reheating of steam, despite the complexity of the boiler and turbine design and a significant increase in the number of steam pipelines, has great economic advantages over boilers without reheating of steam. The steam consumption for the turbine is approximately halved, while the fuel consumption is reduced by 4–5%. The presence of intermediate superheating of steam also reduces the moisture content of the steam in the last stages of the turbine, due to which the wear of the blades by water droplets decreases and the efficiency of the LPC of the turbine slightly increases.

Further, in the tail section of the boiler, there are auxiliary surfaces designed to use the heat of flue gases. This convection part of the boiler contains a water economizer. 8, where the feed water is heated before entering the drum, and the air heater 9, used for heating air before supplying it to the burners and to the dust preparation circuit, which increases the efficiency of the PC. Cooled flue gases with a temperature of 120–150 ° C are sucked out by a smoke exhauster into the chimney.

Further improvement of water-tube PC made it possible to create a PC consisting entirely of steel pipes of small diameter, into which water under pressure enters from one end, and steam of specified parameters comes out from the other - the so-called direct-flow boiler (fig. 3.9). Thus, this is a PC, in which the complete evaporation of water occurs during a single (direct-flow) passage of water through the evaporating heating surface. In the direct-flow PC, water is supplied by a feed pump through an economizer. There is no drum or standpipes in such a boiler.

Rice. 3.9. Schematic diagram of a direct-flow PC:

1 - screens of the lower radiation part; 2 - burners; 3 - screens of the upper radiation part; 4 - screen steam superheater; 5 –Convective superheater; 6 - secondary superheater; 7 - water economizer; 8 - feed water supply; 9 - steam removal to the turbine; 10 - steam supply from HPC for secondary overheating; 11 - steam removal to the central heating system after secondary overheating; 12 - discharge of flue gases to the air heater
The heating surface of the boiler can be thought of as a series of parallel coils, in which the water heats up as it moves, turns into steam, and then the steam is overheated to the required temperature. These coils are located both on the walls of the combustion chamber and in the boiler gas ducts. Combustion devices, secondary superheater and air preheater of once-through boilers do not differ from drum boilers.

In drum boilers, as the water evaporates, the concentration of salts in the remaining boiler water increases, and a small proportion of this boiler water in an amount of about 0.5% must be discharged from the boiler all the time in order to prevent the salt concentration from building up above a certain limit. This process is called blowdown boiler. For once-through boilers, this method of removing accumulated salts is inapplicable due to the lack of water volume, and therefore the feed water quality standards for them are much more stringent.

Another disadvantage of direct-flow PCs is the increased energy consumption for the feed pump drive.

Direct-flow PCs are installed, as a rule, on a condensation power plants where the boilers are powered by demineralized water. Their use at combined heat and power plants is associated with increased costs for chemical treatment of additional (make-up) water. The most effective direct-flow PS for supercritical pressures (above 22 MPa), where other types of boilers are inapplicable.

In power units, either one boiler is installed per turbine ( monoblocks), or two boilers of half capacity. To the benefits double-blocks can be attributed to the possibility of operation of the unit with half load on the turbine in the event of damage to one of the boilers. However, the presence of two boilers in the block significantly complicates the entire circuit and control of the block, which in itself reduces the reliability of the block as a whole. In addition, operating the unit at half load is very uneconomical. The experience of a number of stations has shown that monoblocks can operate no less reliably than double-blocks.

In block installations for pressure up to 130 kgf / cm 2 (13 MPa) both drum and direct-flow boilers are used. In installations for a pressure of 240 kgf / cm 2 (24 MPa) and higher only direct-flow boilers are used.

Heating boiler - This is a boiler unit of a combined heat and power plant (CHP), which provides a simultaneous supply of steam to heating turbines and the production of steam or hot water for technological, heating and other needs. In contrast to KES boilers, in heating boilers, the returned contaminated condensate is usually used as a water feeder. For such operating conditions, drum-type boilers with staged evaporation are most suitable. In most CHP plants, cogeneration boilers are cross-linked by steam and water. Drum boilers with a steam capacity of 420 t / h (steam pressure 14 MPa, temperature 560 ºС) are the most common in the Russian Federation at CHPPs. Since 1970, monoblocks with once-through boilers with a steam capacity of 545 t / h (25 MPa , 545 ° C).

Cogeneration PCs also include peak hot water boilers, which are used for additional heating of water with an increase in heat load in excess of the maximum provided by the extraction of turbines. In this case, the water is heated first by steam in boilers to 110–120 ºС, and then in boilers to 150–170 ºС. In our country, these boilers are usually installed next to the main building of the CHPP. The use of comparatively cheap peak hot water heating boilers for removing short-term peaks of heat loads allows to dramatically increase the number of hours of use of the main heating equipment and to increase the efficiency of its operation.

For heat supply of residential areas, water-heating gas-oil boilers of the KVGM type, operating on gas, are often used. Fuel oil is used as a reserve fuel for such boilers, for heating of which gas-oil drum steam boilers are used.

3.1.4.2. Steam turbines
Steam turbine(PT) is a heat engine in which the potential energy of the steam is converted into kinetic energy of the steam jet, and the latter is converted into mechanical energy of the rotor rotation.

They tried to create a PT for a long time. Known is the description of the primitive PT, made by Heron of Alexandria (1st century BC). However, only at the end of the 19th century, when thermodynamics, mechanical engineering and metallurgy reached a sufficient level, K.G. Laval (Sweden) and C.A. Parsons (Great Britain) independently created industrially suitable PTs in 1884-1889.

Laval applied steam expansion in conical fixed nozzles in one step from initial to final pressure and directed the resulting jet (with a supersonic outflow velocity) onto one row of rotor blades mounted on a disk. PTs operating on this principle are called active Fri. The impossibility of obtaining high aggregate power and the very high rotational speed of single-stage Laval PTs (up to 30,000 rpm for the first samples) led to the fact that they retained their importance only for the drive of auxiliary mechanisms.

Parsons created a multistage reactive PT, in which the expansion of steam was carried out in a large number of successively located stages, not only in the channels of the stationary (guide) blades, but also between the movable (working) blades. The Parsons' rocket tank was used for some time mainly on warships, but gradually gave way to more compact combined active-reactive PTs, in which the high-pressure reactive part is replaced by an active disk. As a result, losses due to steam leakage through the gaps in the blade apparatus have decreased, the turbine has become simpler and more economical.

Active FH power plants developed in the direction of creating multistage structures, in which the expansion of steam was carried out in a number of successively located stages. This made it possible to significantly increase the unit power of the PT, while maintaining a moderate rotational speed required for direct connection of the PT shaft with the mechanism it rotates, in particular, an electric generator.

There are several options for the design of steam turbines, allowing them to be classified according to a number of characteristics.

In the direction of travel steam flow distinguish axial PTs, in which the steam flow moves along the axis of the turbine, and radial PTs, the direction of the steam flow in which is perpendicular, and the rotor blades are parallel to the axis of rotation. In the Russian Federation, only axial PTs are built.

By the number of bodies (cylinders) PT is subdivided into monohull, double-hull and three-case(with high, medium and low pressure cylinders) . The multi-casing design allows the use of large available enthalpy differences by placing a large number of pressure stages, the use of high-quality metals in the high-pressure part and the bifurcation of the steam flow in the low-pressure part. At the same time, such a PT turns out to be more expensive, heavy and complex.

According to the number of shafts distinguish single-shaft PT, in which the shafts of all housings are on the same axis, as well as twin-shaft or three-shaft, consisting of two or three parallel-placed single-shaft PTs, connected by a common thermal process, and in ship PTs also by a common gear transmission (reducer).

The stationary part of the PT (housing) is split in the horizontal plane for the possibility of mounting the rotor. The body has grooves for installing diaphragms, the connector of which coincides with the plane of the body connector. Along the periphery of the diaphragms, there are nozzle channels formed by curved blades that are poured into the body of the diaphragms or welded to it. In places where the shaft passes through the walls of the housing, labyrinth-type end seals are installed to prevent steam leaks outward (from the high pressure side) and air suction into the housing (from the low side). Labyrinth seals are also installed in the places where the rotor passes through the diaphragms in order to avoid steam flow from stage to stage bypassing the nozzles. A limit regulator (safety regulator) is installed at the front end of the shaft, which automatically stops the PT when the speed increases by 10-12% above the nominal. The rear end of the rotor is equipped with a barring device with an electric drive for slow (4–6 rpm) rotation of the rotor after stopping the PT, which is necessary for its uniform cooling.

In fig. 3.10 schematically shows the device of one of the intermediate stages of a modern steam turbine at a TPP. The stage consists of a disc with blades and a diaphragm. The diaphragm is a vertical partition between two discs, in which stationary guide vanes are located along the entire circumference against the rotor blades, forming nozzles for steam expansion. The diaphragms are made of two horizontally split halves, each of which is fixed in the corresponding half of the turbine housing.

Rice. 3.10. Device of one of the stages of multistage

turbines: 1 - shaft; 2 - disk; 3 - working blade; 4 - the wall of the turbine cylinder; 5 - nozzle grill; 6 - diaphragm;

7 - diaphragm seal
A large number of stages forces the turbine to be made of several cylinders, placing 10-12 stages in each. Turbines with reheating of steam in the first high pressure cylinder (HPC) usually have a group of stages that convert the energy of the steam from the initial parameters to the pressure at which the steam is supplied for reheating. After the reheating of steam in turbines with a capacity of 200 and 300 MW, steam is supplied to two more cylinders - the LPC and the LPC.

The technological process of converting the feedstock (fuel) into the final product (electricity) is reflected in the technological schemes of power plants.

Process flow diagram of a coal-fired TPP is shown in Figure 3.4. It is a complex complex of interconnected paths and systems: a dust preparation system; fuel supply and fuel ignition system (fuel path); ash removal system; gas-air tract; a steam-water path system, including a steam-water boiler and a turbine unit; system for preparation and supply of additional water to replenish feed water losses; technical water supply system for steam cooling; system of network water heating installations; electric power system, including a synchronous generator, step-up transformer, high-voltage switchgear, etc.

Below is a brief description of the main systems and paths of the technological scheme of a TPP using the example of a coal-fired TPP.

Rice. 3.3. Process flow diagram of a pulverized coal power plant

1. Dust preparation system. Fuel path... Solid fuel delivery is carried out by rail in special open wagons 1 (see fig. 3.4). Gondola cars with coal are weighed on railway scales. In winter, gondola cars with coal are passed through a defrosting hothouse, in which the gondola car walls are heated with heated air. Next, the gondola car is pushed into an unloading device - a car dumper 2 , in which it rotates around the longitudinal axis at an angle of about 180 0; the coal is discharged onto the grates overlapping the receiving bunkers. Coal from bunkers is fed by feeders to a conveyor 4 , through which it enters either the coal warehouse 3 , or through the crushing department 5 in the raw coal bunker boiler room 6 , which can also be delivered from a coal warehouse.

From the crushing plant, the fuel enters the raw coal bunker 6 , and from there through the feeders to the pulverized coal mills 7 ... Coal dust is pneumatically conveyed through a separator 8 and cyclone 9 into the coal dust bin 10 , and from there feeders 11 supplied to the burners. The air from the cyclone is sucked in by the mill fan 12 and is fed into the boiler combustion chamber 13 .

This entire fuel path, together with the coal storage, belongs to the fuel supply system, which is maintained by the personnel of the fuel and transport department of the TPP.

Pulverized coal boilers must also have a starting fuel, usually fuel oil. Fuel oil is delivered in railway tanks, in which it is heated by steam before being discharged. With the help of the first and second lift pumps, it is supplied to the oil injectors. The starting fuel can also be natural gas coming from the gas pipeline through the gas control point to the gas burners.

At TPPs that burn gas and oil fuel, the fuel economy is significantly simplified in comparison with pulverized coal TPPs. The coal storage, the crushing department, the conveyor system, the raw coal and dust bunker, as well as the ash collection and ash removal systems are becoming unnecessary.

2... Air-gas path. Slag ash removal system. The air required for combustion is supplied to the air duct.

blower steam boiler heaters 14 ... Air is usually taken from the upper part of the boiler room and (with steam boilers of high capacity) from the outside of the boiler room.

The gases formed during combustion in the combustion chamber, after leaving it, pass sequentially through the gas ducts of the boiler plant, where in the superheater (primary and secondary, if a cycle with intermediate superheating of steam is carried out) and the water economizer give heat to the working fluid, and the air heater - supplied to the steam boiler air. Then in ash collectors (electrostatic precipitators) 15 gases are cleaned from fly ash and through the chimney 17 smoke exhausters 16 released into the atmosphere.

Slag and ash falling out under the combustion chamber, air heater and ash collectors are washed off with water and fed through channels to dredging pumps 33 , which pump them into ash dumps.

3... Steam-water tract. Steam superheated in a superheater from a steam boiler 13 through steam lines and a nozzle system to the turbine 22 .

Condensate from condenser 23 turbines are supplied by condensate pumps 24 through regenerative low pressure heaters 18 into the deaerator 20 , in which the water is brought to a boil; at the same time, it is freed from the aggressive gases O 2 and CO 2 dissolved in it, which prevents corrosion in the steam-water path. From the deaerator, water is supplied by feed pumps 21 through high pressure heaters 19 into the boiler economizer, providing preheating of water and significantly increasing the efficiency of the TPP.

The steam-water path of the TPP is the most complex and responsible, since this path has the highest metal temperatures and the highest steam and water pressures.

To ensure the functioning of the steam-water tract, a system for the preparation and supply of additional water to replenish the losses of the working fluid is required, as well as a system of technical water supply of the TPP to supply cooling water to the turbine condenser.

4... Additional water preparation and supply system. Additional water is obtained as a result of chemical purification of raw water, carried out in special ion-exchange filters for chemical water purification.

Steam and condensate losses due to leaks in the steam-water path are replenished in this scheme with chemically demineralized water, which is supplied from the demineralized water tank by a transfer pump to the condensate line behind the turbine condenser.

Devices for chemical treatment of make-up water are located in the chemical workshop 28 (chemical water treatment shop).

5... Steam cooling system. Cooling water is supplied to the condenser from the water supply receiving well 26 circulation pumps 25 ... The cooling water heated in the condenser is discharged into the collection well 27 the same source of water at a certain distance from the place of intake, sufficient so that the heated water does not mix with the intake.

In many technological schemes of thermal power plants, cooling water is pumped through the condenser tubes by circulation pumps. 25 and then enters the cooling tower (cooling tower), where, due to evaporation, the water is cooled by the same temperature difference by which it was heated in the condenser. The water supply system with cooling towers is mainly used at CHP plants. IES uses a water supply system with cooling ponds. With evaporative cooling of water, the vapor is approximately equal to the amount of steam condensing in the turbine condensers. Therefore, replenishment of the water supply systems is required, usually with water from the river.

6. System of networked water heating installations. The schemes may include a small network heating unit for heating the power plant and the adjacent village. To network heaters 29 In this unit, steam comes from the turbine extractions, condensate is removed through the line 31 ... Mains water is supplied to the heater and removed from it through pipelines 30 .

7. Electrical power system. An electric generator rotated by a steam turbine generates an alternating electric current, which goes through a step-up transformer to the busbars of the open switchgear (OSG) of the TPP. Busbars of the auxiliary system are also connected to the generator terminals through an auxiliary transformer. Thus, the consumers of the auxiliary needs of the power unit (electric motors of auxiliary units - pumps, fans, mills, etc.) are powered by the generator of the power unit. To supply electric power to electric motors, lighting devices and devices of the power plant, there is an electrical switchgear for auxiliary needs 32 .

In special cases (emergency situations, load shedding, start-up and shutdowns), auxiliary power supply is provided through the standby switchgear bus transformer. Reliable power supply of electric motors of auxiliary units ensures the reliability of operation of power units and TPPs as a whole. Interruption of power supply for own needs leads to failures and accidents.

The fundamental difference between the technological scheme of a gas turbine power plant (GTU) and a steam turbine one is that in a GTU the chemical energy of the fuel is converted into mechanical energy in one unit - a gas turbine, as a result of which there is no need for a steam boiler.

The gas turbine unit (Fig. 3.5) consists of a combustion chamber, a gas turbine GT, an air compressor K and an electric generator G. Compressor K sucks in atmospheric air, compresses it to an average of 6-10 kg / cm 2 and supplies it to the combustion chamber of the combustor. Fuel (for example, diesel oil, natural or industrial gas) also gets into the combustion chamber and is burned in compressed air.



Rice. 3.4. Simplified process flow diagram of a gas turbine

power plants on liquid or gas fuel: T - fuel; V -

air; КС - combustion chamber; GT - gas turbine; K - air compressor; G - electric generator

Hot gases with a temperature of 600–800 ° С from the combustion chamber enter the GT gas turbine. Passing through the turbine, they expand to atmospheric pressure and, moving at high speed between the blades, rotate the turbine shaft. Exhaust gases are discharged through the exhaust pipe into the atmosphere. A significant portion of the power of a gas turbine is expended in rotating the compressor and other auxiliary devices.

The main advantages of gas turbine units in comparison with steam turbine units are:

1) lack of a boiler plant and chemical water treatment;

2) significantly less demand for cooling water, which makes it possible to use GTU in areas with limited water resources;

3) significantly fewer operating personnel;

4) quick start-up;

5) lower cost of generated electricity.

Layout diagrams of TPP

TPPs by type (structure) of the thermal scheme are subdivided into block and non-block.

With a block scheme All the main and auxiliary equipment of the plant has no technological connections with the equipment of another plant of the power plant. In fossil fuel power plants, steam is supplied to each turbine only from one or two connected boilers. A steam turbine plant, the turbine of which is powered by steam from one steam boiler, is called monoblock, in the presence of two boilers for one turbine - double-block.

With a non-block diagram TPP steam from all steam boilers enters a common mainline and only from there is distributed to individual turbines. In some cases, it is possible to direct steam directly from steam boilers to turbines, however, the common connecting line is preserved, so you can always use steam from all boilers to power any turbine. The lines carrying water to the steam boilers (feed lines) are also cross-linked.

Block TPPs are cheaper than non-block ones, since the pipeline diagram is simplified and the number of fittings is reduced. It is easier to control individual units at such a station, block-type installations are easier to automate. In operation, the work of one block does not affect the neighboring blocks. When expanding the power plant, the subsequent unit can have a different capacity and operate at new parameters. This makes it possible to install more powerful equipment with higher parameters at the expandable station, i.e. allows to improve the equipment and improve the technical and economic indicators of the power plant. At the same time, the processes of setting up new equipment do not affect the operation of previously installed units. However, for normal operation of block TPPs, the reliability of their equipment should be much higher than that of non-block ones. There are no standby steam boilers in the units; if the possible productivity of the boiler is higher than the flow rate required for a given turbine, part of the steam (the so-called hidden reserve, which is widely used at non-block TPPs) cannot be transferred here to another unit. For steam turbine plants with intermediate superheating of steam, the block scheme is practically the only possible one, since the non-block scheme of the station in this case will turn out to be overly complicated.

In our country, steam turbine units of TPPs without controlled extraction of steam with an initial pressure P 0 ≤8.8 MPa and installations with controlled extractions at P 0 ≤12.7 MPa, operating in cycles without intermediate superheating of steam, are built non-block. At higher pressures (at KES at P 0 ≥12.7 MPa, and at CHPP at P 0 = 23.5 MPa) all steam turbine units operate in cycles with reheating, and stations with such installations are built in modular units.

The main building (main building) houses the main and auxiliary equipment directly used in the technological process of the power plant. The mutual arrangement of equipment and building structures is called the layout of the main building of the power plant.

The main building of a power plant usually consists of a turbine room, a boiler room (with a bunker room for solid fuel operation) or a reactor room at a nuclear power plant and a deaerator room. In the engine room, along with the main equipment (primarily turbine units), there are: condensate pumps, regenerative low and high pressure heaters, feed pumping units, evaporators, steam converters, network heaters (at CHP), auxiliary heaters and other heat exchangers.

In a warm climate (for example, in the Caucasus, Central Asia, etc.), in the absence of significant atmospheric precipitation, dust storms, etc. at IES, especially gas and oil, open equipment is used. At the same time, sheds are arranged over the boilers, the turbine units are protected with light shelters; the auxiliary equipment of the turbine unit is placed in a closed condensation room. The specific cubic capacity of the main building of the IES with an open layout is reduced to 0.2–0.3 m 3 / kW, which makes the construction of the IES cheaper. Overhead cranes and other lifting mechanisms are installed in the premises of the power plant for the installation and repair of power equipment.

In fig. 3.6. the layout diagram of the power unit of the pulverized-coal power plant is shown: I - room for steam generators; II - machine room, III - cooling water pumping station; 1 - unloading device; 2 - crushing plant; 3 - water economizer and air heater; 4 - steam superheaters; 5 , 6 - combustion chamber; 7 - pulverized coal burners; 8 –The steam generator; 9 - mill fan; 10 - bunker of coal dust; 11 - dust feeders; 12 - pipelines for reheat steam; 13 - deaerator; 14 - steam turbine; 15 - electric generator; 16 - a step-up electrical transformer; 17 - capacitor; 18 - supply and drain pipelines of cooling water; 19 - condensate pumps; 20 - regenerative HDPE; 21 - feed pump; 22 - regenerative LDPE; 23 - blower fan; 24 - ash collector; 25 - slag and ash channels; EE- high voltage electricity.

In fig. 3.7 shows a simplified layout diagram of a gas-oil power plant with a capacity of 2400 MW, indicating the location of only the main and part of the auxiliary equipment, as well as the dimensions of the structures (m): 1 - boiler room; 2 –Turbine department; 3 - condenser compartment; 4 - generator compartment; 5 - deaerator department; 6 - blower fan; 7 - regenerative air heaters; 8 - auxiliary switchgear (RUSN); 9 - chimney.



Rice. 3.7. Layout of the main building of the gas-oil

power plants with a capacity of 2400 MW

The main equipment of the IES (boiler and turbine units) is located in the main building, boilers and a pulverized plant (at IESs that burn, for example, coal in the form of dust) - in the boiler room, turbine units and their auxiliary equipment - in the turbine room of the power plant. At the IES, mainly one boiler is installed per turbine. The boiler with the turbine unit and their auxiliary equipment form a separate part - the monoblock of the power plant.

For turbines with a capacity of 150–1200 MW, boilers with a capacity of 500–3600 m 3 / h of steam, respectively, are required. Previously, the state district power station used two boilers per turbine, i.e. double-blocks . At the IES without intermediate superheating of steam with turbine units with a capacity of 100 MW or less, a non-block centralized scheme was used, in which steam from the boilers is diverted into a common steam line, and from it is distributed between the turbines.

The dimensions of the main building depend on the capacity of the equipment placed in it: the length of one block is 30–100 m, the width is 70–100 m. The height of the turbine hall is about 30 m, the boiler room is 50 m more. The efficiency of the layout of the main building is estimated approximately by the specific cubic capacity, which is about 0.7-0.8 m 3 / kW at a pulverized coal power plant. , and at the gas-oil plant - about 0.6–0.7 m 3 / kW. Part of the auxiliary equipment of the boiler room (smoke exhausters, blowing fans, ash collectors, dust cyclones and dust separators of the dust preparation system) are often installed outside the building, in the open air.

IES is built directly at water supply sources (river, lake, sea); often a reservoir (pond) is created next to the IES. On the territory of the IES, in addition to the main building, structures and devices for technical water supply and chemical water treatment, fuel facilities, electrical transformers, switchgears, laboratories and workshops, material warehouses, office premises for personnel serving the IES are located. Fuel is usually delivered to the IES territory by train. Ash and slag from the combustion chamber and ash collectors are removed hydraulically. On the territory of the IES, railways and highways are laid, power transmission lines, engineering ground and underground communications are being constructed. The area of ​​the territory occupied by the IES facilities is, depending on the power plant capacity, fuel type and other conditions, 25–70 hectares .

Large-scale pulverized coal-fired power plants in Russia are serviced by personnel at the rate of 1 person for every 3 MW of capacity (approximately 1000 people at IES with a capacity of 3,000 MW); in addition, maintenance personnel are required.

The capacity of the IES depends on water and fuel resources, as well as the requirements of environmental protection: ensuring the normal cleanliness of the air and water basins. Emissions with fuel combustion products in the form of solid particles into the air in the area of ​​the IES operation are limited by the installation of perfect ash collectors (electrostatic precipitators with an efficiency of about 99%). The remaining impurities, oxides of sulfur and nitrogen, are dispersed by means of high chimneys, which are built to remove harmful impurities into the higher layers of the atmosphere. Chimneys up to 300 m or more in height are constructed of reinforced concrete or with 3-4 metal trunks inside a reinforced concrete shell or a common metal frame.

Controlling a wide variety of IES equipment is possible only on the basis of comprehensive automation of production processes. Modern condensing turbines are fully automated. The boiler unit has automated control over the processes of fuel combustion, supplying the boiler unit with water, maintaining the temperature of steam overheating, etc. Other processes of the IES are also automated: maintaining the specified operating modes, starting and stopping units, protecting equipment in case of abnormal and emergency conditions.

YOUTH AND SPORT OF UKRAINE

NS.A... GICHEV

THERMAL POWER PLANTS

Oftenb I

Dnipropetrovsk NMetAU 2011

MINISTRY OF EDUCATION AND SCIENCE,

YOUTH AND SPORT OF UKRAINE

NATIONAL METALLURGICAL ACADEMY OF UKRAINE

NS.A... GICHEV

THERMAL POWER PLANTS

Oftenb I

Ill. 23. Bibliography: 4 names.

Responsible for the release, Dr. Sciences, prof.

Reviewers: Dr. Tech. Sciences, prof. (DNUZHT)

Cand. tech. Sciences, Assoc. (NMetAU)

© National Metallurgical

Academy of Ukraine, 2011

INTRODUCTION ……………………………………………………………………… ..4

1 GENERAL INFORMATION ABOUT THERMAL POWER PLANTS ……………… ... 5

1.1 Definition and classification of power plants ………………………… .5

1.2 Process flow diagram of a thermal power plant ............................................................. 8


1.3 Technical and economic indicators of TPPs ……………………………… .11

1.3.1 Energy indicators …………………………………… .11

1.3.2 Economic indicators …………………………………… .13

1.3.3 Performance indicators ……………………………… ... 15

1.4 Requirements for TPPs ……………………………………… 16

1.5 Features of industrial thermal power plants ……………… 16

2 CONSTRUCTION OF THERMAL CIRCUITS OF TPPs ............................................. 17

2.1 General concepts of thermal circuits ……………………………………… 17

2.2 Initial parameters of steam ……………………………………………… .18

2.2.1 Initial steam pressure ……………………………………… .18

2.2.2 Initial steam temperature ………………………………… ... 20

2.3 Intermediate superheating of steam ………………………………………… ..22

2.3.1 Energy efficiency of reheating ... 24

2.3.2 Intermediate superheat pressure ………………………… 26

2.3.3 Technical implementation of reheating ... ... 27

2.4 Final parameters of steam …………………………. …………………… .29

2.5 Regenerative heating of feed water ………………………… ... 30

2.5.1 Energy efficiency of regenerative heating ... 30

2.5.2 Technical implementation of regenerative heating ... .... 34

2.5.3 Temperature of the regenerative feed water heating ... 37

2.6 Construction of thermal power plants based on the main types of turbines …… ..39

2.6.1 Construction of a thermal circuit based on the turbine "K" ... ... ... ... ... 39

2.6.2 Construction of a thermal circuit based on the turbine "T" .... ……… ..41

REFERENCES ………………………………………………………………… ... 44

INTRODUCTION

For a number of reasons, the discipline "Thermal Power Plants" is of particular importance among the disciplines taught for the specialty 8 (7). - heat power engineering.

First, from a theoretical point of view, the discipline accumulates the knowledge gained by students in almost all the main previous disciplines: "Fuel and its combustion", "Boiler plants", "Blowers and heat engines", "Sources of heat supply for industrial enterprises" , "Gas cleaning" and others.

Second, from a practical point of view, thermal power plants (TPPs) are a complex energy enterprise that includes all the main elements of the energy economy: a fuel preparation system, a boiler shop, a turbine shop, a system for converting and supplying thermal energy to external consumers, utilization and neutralization systems. harmful emissions.

Third, from an industrial point of view, TPPs are the dominant power generating enterprises in the domestic and foreign energy sector. Thermal power plants account for about 70% of the installed electricity generating capacity in Ukraine, and taking into account nuclear power plants, where steam turbine technologies are also implemented, the installed capacity is about 90%.

This lecture notes were developed in accordance with the work program and curriculum for specialty 8 (7). - heat power engineering and as the main topics includes: general information about thermal power plants, principles of constructing thermal power plant circuits, selection of equipment and calculations of thermal circuits, equipment layout and operation of thermal power plants.

The discipline "Thermal Power Plants" contributes to the systematization of the knowledge gained by students, the expansion of their professional horizons and can be used when performing term papers in a number of other disciplines, as well as in the preparation of graduate works of specialists and graduate works of masters.


1 GENERAL INFORMATION ABOUT THERMAL POWER PLANTS

1.1 Definition and classification of power plants

Power station- an energy company designed to convert various types of fuel and energy resources into electricity.

The main options for the classification of power plants:

I. Depending on the type of converted fuel and energy resources:

1) thermal power plants (TPP), in which electricity is obtained by converting hydrocarbon fuels (coal, natural gas, fuel oil, combustible VER and others);

2) nuclear power plants (NPP), in which electricity is obtained by converting atomic energy into nuclear fuel;

3) hydroelectric power plants (HPPs), in which electricity is obtained by converting the mechanical energy of the flow of a natural source of water, primarily rivers.

This classification option can also include power plants using non-traditional and renewable energy sources:

· Solar power plants;

· Geothermal power plants;

· Wind power plants;

· Tidal power plants and others.

II. For this discipline, a more in-depth classification of thermal power plants is of interest, which, depending on the type of heat engines, are divided into:

1) steam turbine power plants (PTU);

2) gas turbine power plants (GTU);

3) combined-cycle power plants (CGE);

4) power plants on internal combustion engines (ICE).

Among these power plants, steam turbine power plants are dominant, accounting for over 95% of the total installed capacity of TPPs.

III. Depending on the type of energy sources supplied to an external consumer, steam turbine power plants are divided into:

1) condensing power plants (IES) that supply the external consumer exclusively with electricity;

2) combined heat and power plants (CHP), supplying the external consumer with both thermal and electrical energy.

IV. Depending on the purpose and departmental subordination, power plants are divided into:

1) district power plants, which are designed to provide electricity to all consumers in the district;

2) industrial power plants, which are part of industrial enterprises and are designed to provide electricity primarily to consumers of enterprises.

V. Depending on the duration of use of the installed capacity during the year, power plants are divided into:

1) basic (B): 6000 ÷ 7500 h / year, i.e. over 70% of the length of the year;

2) semi-basic (P / W): 4000 ÷ 6000 h / year, 50 ÷ 70%;

3) half-peak (P / P): 2000 ÷ 4000 h / year, 20 ÷ 50%;

4) peak (P): up to 2000 h / year, up to 20% of the length of the year.

This classification option can be illustrated by the example of a graph of the duration of electrical loads:

Figure 1.1 - Graph of duration of electrical loads

Vi. Depending on the pressure of the steam entering the turbines, steam turbine TPPs are divided into:

1) low pressure: up to 4 MPa;

2) medium pressure: up to 9 - 13 MPa;

3) high pressure: up to 25 - 30 MPa, including:

● subcritical pressure: up to 18 - 20 MPa

● critical and supercritical pressure: over 22 MPa

Vii. Depending on the capacity, steam turbine power plants are divided into:

1) power plants of low power: total installed capacity up to 100 MW with a unit capacity of installed turbine generators up to 25 MW;

2) average power: total installed power up to 1000 MW with unit capacity of installed turbine generators up to 200 MW;

3) high power: total installed capacity over 1000 MW with a unit capacity of installed turbine generators over 200 MW.

VIII. Depending on the method of connecting steam generators to turbine generators, thermal power plants are divided into:

1) centralized (non-block) TPPs, in which steam from all boilers enters one central steam pipeline, and then is distributed among the turbine generators (see Fig. 1.2);

1 - steam generator; 2 - steam turbine; 3 - central (main) steam pipeline; 4 - steam turbine condenser; 5 - electric generator; 6 - transformer.

Figure 1.2 - Schematic diagram of a centralized (non-block) TPP

2) block TPPs, in which each of the installed steam generators is connected to a well-defined turbine generator (see Figure 1.3).

1 - steam generator; 2 - steam turbine; 3 - intermediate superheater; 4 - steam turbine condenser; 5 - electric generator; 6 - transformer.

Figure 1.3 - Schematic diagram of a block TPP

In contrast to the non-block block diagram of a TPP, it requires less capital expenditures, is easier to operate and creates conditions for the complete automation of the steam turbine unit of the power plant. The block scheme reduces the number of pipelines and production volumes of the station for equipment placement. When using intermediate superheating of steam, the use of block schemes is mandatory, since otherwise it is not possible to control the flow of steam supplied from the turbine for superheating.

1.2 Technological diagram of a thermal power plant

The technological diagram depicts the main parts of the power plant, their interconnection and, accordingly, shows the sequence of technological operations from the moment the fuel is delivered to the station to the supply of electricity to the consumer.

As an example, Figure 1.4 shows the process flow diagram of a pulverized coal steam turbine power plant. This type of TPP prevails among operating basic thermal power plants in Ukraine and abroad.

Sun - fuel consumption at the station; Dp. g - productivity of the steam generator; Ds. n. - conditional steam consumption for the station's own needs; Дт - steam consumption for the turbine; Evir - the amount of electricity generated; Esn - electricity consumption for the station's own needs; Eotp - the amount of electricity supplied to an external consumer.

Figure 1.4 - An example of a technological scheme of a steam turbine pulverized coal power plant

It is customary to divide the technological scheme of a TPP into three parts, which are marked with dotted lines in Figure 1.4:

I Fuel-gas-air path, which includes:

1 - fuel economy (unloading device, raw coal warehouse, crushing plants, crushed coal bunkers, cranes, conveyors);

2 - dust preparation system (coal mills, small fans, coal dust bins, feeders);

3 - blower fan for air supply for fuel combustion;

4 - steam generator;

5 - gas cleaning;

6 - smoke exhauster;

7 - chimney;

8 - dredge pump for transportation of hydro-ash and slag mixture;

9 - supply of the hydro-ash and slag mixture for utilization.

In general, the fuel-gas-air path includes : fuel economy, dust preparation system, draft equipment, boiler gas ducts and ash and slag removal system.

II Steam-water tract, which includes:

10 - steam turbine;

11 - steam turbine condenser;

12 - circulation pump of the circulating water supply system for cooling the condenser;

13 - cooling device of the circulating system;

14 - supply of additional water to compensate for water losses in the circulating system;

15 - supply of raw water for the preparation of chemically treated water, which compensates for condensate losses at the station;

16 - chemical water treatment;

17 - chemical water treatment pump supplying additional chemically treated water to the exhaust steam condensate stream;

18 - condensate pump;

19 - regenerative low pressure feed water heater;

20 - deaerator;

21 - feed pump;

22 - regenerative high pressure feed water heater;

23 - drainage pumps for draining heating steam condensate from the heat exchanger;

24 - regenerative steam extraction;

25 - an intermediate superheater.

In general, the steam-water path includes: steam-water part of the boiler, turbine, condensate unit, systems for the preparation of cooling circulating water and additional chemically purified water, a system for regenerative heating of feed water and deaeration of feed water.

III Electrical part, which includes:

26 - electric generator;

27 - a step-up transformer for electricity supplied to an external consumer;

28 - busbars of the open switchgear of the power plant;

29 - a transformer for electric power for auxiliary needs of the power plant;

30 - busbars of the switchgear for auxiliary power.

Thus, the electrical part includes: electric generator, transformers and switchgear busbars.

1.3 Technical and economic indicators of TPP

Technical and economic indicators of TPPs are divided into 3 groups: energy, economic and operational, which, respectively, are designed to assess the technical level, efficiency and quality of plant operation.

1.3.1 Energy indicators

The main energy indicators of TPPs include: c.p.d. power plants (), specific heat consumption (), specific fuel consumption for electricity generation ().

These indicators are called indicators of the thermal efficiency of the plant.

Based on the results of the actual operation of the power plant, efficiency is determined by the ratios:

; (1.1)

; (1.2)

When designing a power plant and for analyzing its operation, efficiency are determined by works that take into account efficiency. individual elements of the station:

where ηcote, ηturb - efficiency boiler and turbine shops;

ηт. p. - c. p. heat flow, which takes into account the heat loss by heat carriers inside the station due to the transfer of heat to the environment through the walls of the pipeline and heat carrier leaks, ηт. p. = 0.98 ... 0.99 (cf. 0.985);

esn - the share of electricity consumed for the power plant's own needs (electric drive in the fuel preparation system, drive of draft means of the boiler shop, drive of pumps, etc.), esn = ESN / Evyr = 0.05 ... 0.10 (cf. 0.075);

qсн - the share of heat consumption for auxiliary needs (chemical water treatment, deaeration of feed water, operation of steam ejectors, providing vacuum in the condenser, etc.), qсн = 0.01 ... 0.02 (cf. 0.015).

K. p.d. the boiler shop can be represented as a c. p.d. steam generator: ηkot = ηp. year = 0.88 ... 0.96 (cf. 0.92)

K. p.d. a turbine shop can be thought of as an absolute electrical efficiency. turbine generator:

ηturb = ηt. r = ηt ηoi ηm, (1.5)

where ηt is the thermal efficiency. steam turbine unit cycle (ratio of used heat to supplied heat), ηt = 0.42 ... 0.46 (cf. 0.44);

ηoi - internal relative efficiency turbine (takes into account losses inside the turbine due to steam friction, crossflows, ventilation), ηoi = 0.76 ... 0.92 (cf. 0.84);

ηm - electromechanical efficiency, which takes into account losses in the transfer of mechanical energy from the turbine to the generator and losses in the generator itself, ηen = 0.98 ... 0.99 (cf. 0.985).

Taking into account the product (1.5), expression (1.4) for the efficiency net power plants takes the form:

ηсnet = ηпг · ηt · ηoi · ηm · ηtp · (1 - eсн) · (1 - qсн); (1.6)

and after substitution of average values ​​will be:

ηсnet = 0.92 · 0.44 · 0.84 · 0.985 · 0.985 · (1 - 0.075) · (1 - 0.015) = 0.3;

In general, for a power plant, the efficiency is the net varies within the range: ηsnet = 0.28 ... 0.38.

Specific heat consumption for electricity generation is determined by the ratio:

, (1.7)

where Qfuel is the heat received from fuel combustion .

; (1.8)

where рн - standard coefficient of efficiency of capital investments, year-1.

The inverse value of ph gives the payback period of the investment, for example, at ph = 0.12 year-1, the payback period will be:

These costs are used to select the most economical option for the construction of a new or reconstruction of an existing power plant.

1.3.3 Performance indicators

Performance indicators assess the quality of operation of a power plant and include, in particular:

1) staffing factor (number of maintenance personnel per 1 MW of the plant's installed capacity), W (person / MW);

2) the utilization factor of the installed capacity of the power plant (the ratio of the actual generation of electricity to the maximum possible generation)

; (1.16)

3) the number of hours of use of the installed capacity

4) equipment availability and equipment technical utilization rate

; (1.18)

Equipment availability factors for boiler and turbine shops are: Kgotkot = 0.96 ... 0.97, Kgotturb = 0.97 ... 0.98.

The utilization factor of equipment for TPPs is: KispTES = 0.85 ... 0.90.

1.4 Requirements for TPP

Requirements for TPPs are divided into 2 groups: technical and economic.

The technical requirements include:

· Reliability (uninterrupted supply of electricity in accordance with the requirements of consumers and the dispatching schedule of electrical loads);

· Maneuverability (the ability to quickly increase or remove the load, as well as start or stop the units);

· Thermal efficiency (maximum efficiency and minimum specific fuel consumption under different operating modes of the station);

· Environmental friendliness (minimum harmful emissions into the environment and not exceeding the permissible emissions under various operating modes of the station).

Economic requirements are reduced to the minimum cost of electricity, provided that all technical requirements are met.

1.5 Features of industrial thermal power plants

Among the main features of industrial thermal power plants should be highlighted:

1) two-way communication of the power plant with the main technological shops (the power plant provides the electrical load for the technological shops and, in accordance with the need, changes the supply of electricity, and the shops in a number of cases are sources of thermal and combustible VER, which are used at power plants);

2) the commonality of a number of systems of power plants and technological workshops of the enterprise (fuel supply, water supply, transport facilities, repair facilities, which reduces the cost of building the station);

3) the presence at industrial power plants, in addition to turbogenerators, turbocompressors and turbo blowers for supplying process gases to the workshops of the enterprise;

4) the prevalence of combined heat and power plants (CHP) in the number of industrial power plants;

5) relatively small capacity of industrial TPPs:

70 ... 80%, ≤ 100 MW.

Industrial TPPs provide 15 ... 20% of the total electricity generation.

2 CONSTRUCTION OF THERMAL CIRCUITS OF TPP

2.1 General concepts of thermal circuits

Thermal diagrams refer to the steam-water paths of power plants and show :

1) the relative position of the main and auxiliary equipment of the station;

2) technological connection of equipment through the lines of the pipeline of heat carriers.

Thermal circuits can be divided into 2 types:

1) fundamental;

2) deployed.

On the schematic diagrams, the equipment is shown to the extent necessary for calculating the thermal circuit and analyzing the calculation results.

Based on the schematic diagram, the following tasks are solved:

1) determine the flow rates and parameters of coolants in various elements of the circuit;

2) choose equipment;

3) develop detailed thermal circuits.

Expanded thermal diagrams include all station equipment, including backup, all station pipelines with shut-off and control valves.

Based on the detailed schemes, the following tasks are solved:

1) mutual placement of equipment in the design of power plants;

2) execution of working drawings during design;

3) operation of stations.

The construction of thermal circuits is preceded by the solution of the following issues:

1) the choice of the type of plant, which is carried out on the basis of the type and number of expected energy loads, i.e. IES or CHP;

2) determine the electrical and thermal capacities of the station as a whole and the capacities of its individual units (units);

3) select the initial and final parameters of the steam;

4) determine the need for intermediate superheating of steam;

5) choose the types of steam generators and turbines;

6) develop a scheme for regenerative heating of feed water;

7) compose the main technical solutions according to the thermal scheme (unit capacity, steam parameters, type of turbines) with a number of auxiliary issues: preparation of additional chemically treated water, deaeration of water, utilization of blowdown water from steam generators, drive of feed pumps and others.

The development of thermal circuits is mainly influenced by 3 factors:

1) the value of the initial and final parameters of steam in a steam turbine installation;

2) intermediate superheating of steam;

3) regenerative heating of feed water.

2.2 Initial steam parameters

The initial steam parameters are the pressure (P1) and temperature (t1) of the steam upstream of the turbine isolation valve.

2.2.1 Initial steam pressure

The initial vapor pressure affects the efficiency. power plants and, first of all, through thermal efficiency. cycle of a steam turbine unit, which in determining the efficiency power plant has a minimum value (ηt = 0.42 ... 0.46):

To determine the thermal efficiency can be used iS- diagram of water vapor (see fig. 2.1):

(2.2)

where Above is the adiabatic heat drop of steam (for an ideal cycle);

qpod - the amount of heat supplied to the cycle;

i1, i2 - steam enthalpy before and after the turbine;

i2 "is the enthalpy of the condensate of the steam discharged in the turbine (i2" = cpt2).

Figure 2.1 - To the determination of the thermal efficiency.

The calculation results using formula (2.2) give the following efficiency values:

ηt, unit fractions

Here 3.4 ... 23.5 MPa are the standard steam pressures adopted for steam turbine power plants in the energy sector of Ukraine.

From the results of the calculation it follows that with an increase in the initial vapor pressure, the value of the efficiency increases. Together with that, an increase in pressure has a number of negative consequences:

1) with an increase in pressure, the volume of steam decreases, the flow area of ​​the turbine flow path and the length of the blades decrease, and, consequently, steam flows increase, which leads to a decrease in the internal relative efficiency. turbines (ηоі);

2) an increase in pressure leads to an increase in steam losses through the end seals of the turbine;

3) the consumption of metal for equipment and the cost of the steam turbine plant increase.

To eliminate negative influence along with an increase in pressure, the turbine power should be increased, which ensures :

1) an increase in steam consumption (excludes a decrease in the flow area in the turbine and the length of the blades);

2) reduces the relative knocking out of steam through mechanical seals;

3) an increase in pressure together with an increase in power makes it possible to make pipelines more compact and reduce metal consumption.

The optimal ratio between the initial steam pressure and the turbine power, obtained on the basis of an analysis of the operation of existing power plants abroad, is shown in Figure 2.2 (the optimal ratio is marked by shading).

Figure 2.2 - Relationship between the power of the turbine generator (N) and the initial steam pressure (P1).

2.2.2 Initial steam temperature

With an increase in the initial steam pressure, the steam moisture at the outlet from the turbine increases, which is illustrated by the graphs on the iS-diagram (see Fig. 2.3).

Р1> Р1 "> Р1" "(t1 = const, P2 = const)

x2< x2" < x2"" (y = 1 – x)

y2> y2 "> y2" "

Figure 2.3 - The nature of the change in the final steam moisture with an increase in the initial steam pressure.

The presence of moisture in the steam increases frictional losses and decreases the internal relative efficiency. and causes drip erosion of the blades and other elements of the flow path of the turbine, which leads to their destruction.

The maximum permissible steam humidity (y2add) depends on the length of the blades (ll); for example:

ll ≤ 750 ... 1000 mm y2dop ≤ 8 ... 10%

ll ≤ 600 mm y2dop ≤ 13%

To reduce the moisture content of the steam, it is necessary to increase its temperature along with an increase in the steam pressure, which is illustrated in Figure 2.4.

t1> t1 "> t1" "(P2 = const)

x2> x2 "> x2" "(y = 1 - x)

y2< y2" < y2""

Figure 2.4 - The nature of the change in the final steam moisture with an increase in the initial steam temperature.

The steam temperature is limited by the heat resistance of the steel from which the superheater, pipelines, and turbine elements are made.

It is possible to use steels of 4 classes:

1) carbon and manganese steels (with the limiting temperature tpr ≤ 450 ... 500 ° С);

2) chromium-molybdenum and chromium-molybdenum-vanadium steels of the pearlite class (tpr ≤ 570 ... 585 ° C);

3) high-chromium steels of the martensite-ferritic class (tpr ≤ 600 ... 630 ° С);

4) stainless chromium-nickel steels of the austenitic class (tpr ≤ 650 ... 700 ° С).

With the transition from one class of steel to another, the cost of equipment rises sharply.

Steel grade

Relative cost

At this stage, from an economic point of view, it is advisable to use pearlitic steel with an operating temperature tp ≤ 540 ° C (565 ° C). Steels of the martensitic-ferritic and austenitic class lead to a sharp increase in the cost of equipment.

The influence of the initial steam temperature on the thermal efficiency should also be noted. cycle of a steam turbine plant. An increase in steam temperature leads to an increase in thermal efficiency:

  • Hydraulic power plants (HPP) and pumped storage (PSPP), using the energy of falling water
  • Nuclear power plants (NPP) using the energy of nuclear decay
  • Diesel power plants (DPP)
  • TPP with gas turbine (GTU) and combined cycle gas turbine (CCGT)
  • Solar power plants (SES)
  • Wind power plants (WPP)
  • Geothermal power plants (GEOTES)
  • Tidal power plants (TPS)
  • Most often in modern energy, traditional and non-traditional energy is distinguished.

    Traditional power engineering is mainly divided into electric power engineering and heat power engineering.

    The most convenient form of energy is electrical, which can be considered the basis of civilization. Conversion of primary energy into electrical energy is carried out at power plants.

    A huge amount of electricity is produced and consumed in our country. It is almost entirely generated by three main types of power plants: thermal, nuclear and hydroelectric power plants.

    Approximately 70% of the world's electricity is generated by thermal power plants. They are divided into condensing thermal power plants (CPS), which generate electricity only, and combined heat and power plants (CHP), which produce electricity and heat.

    In Russia, about 75% of energy is produced at thermal power plants. TPPs are built in areas where fuel is produced or in areas where energy is consumed. It is profitable to build hydroelectric power plants on deep mountain rivers. Therefore, the largest hydroelectric power plants are built on Siberian rivers. Yenisei, Angara. But also cascades of hydroelectric power stations were built on the lowland rivers: Volga, Kama.

    Nuclear power plants were built in areas where a lot of energy is consumed, but other energy resources are not enough (in the western part of the country).

    Thermal power plants (TPPs) are the main type of power plants in Russia. These plants generate approximately 67% of Russia's electricity. Their placement is influenced by fuel and consumer factors. The most powerful power plants are located at fuel extraction sites. TPPs using high-calorie, transportable fuel are consumer-oriented.

    Fig. 1. Schematic diagram of a thermal power plant

    A schematic diagram of a thermal power plant is shown in Fig. 1. It should be borne in mind that several circuits can be envisaged in its design - the coolant from the fuel reactor may not go directly to the turbine, but give its heat in the heat exchanger to the coolant of the next circuit, which can already go to the turbine, and may further transfer its energy to the next contour. Also, in any power plant, a cooling system for the spent heat carrier is provided in order to bring the temperature of the heat carrier to the value required for a repeated cycle. If there is a settlement near the power plant, then this is achieved by using the heat of the spent heat carrier to heat water for heating houses or hot water supply, and if not, then the excess heat of the spent heat carrier is simply discharged into the atmosphere in the cooling towers. Cooling towers are most often used as a condenser for exhaust steam in non-nuclear power plants.

    The main equipment of the TPP is a boiler-steam generator, a turbine, a generator, a steam condenser, and a circulation pump.

    In the boiler of the steam generator, when fuel is burned, thermal energy is released, which is converted into energy of water vapor. In a turbine, the energy of water vapor is converted into mechanical energy of rotation. The generator converts mechanical rotation energy into electrical energy. The scheme of the CHPP differs in that, in addition to electrical energy, it also generates heat by removing part of the steam and heating the water supplied to the heating mains with its help.

    There are thermal power plants with gas turbines. The working fluid and them - gas with air. The gas is released during the combustion of fossil fuel and is mixed with heated air. The air-gas mixture at 750-770 ° C is supplied to the turbine, which rotates the generator. TPP with gas turbine units is more maneuverable, easy to start up, stop, and regulate. But their power is 5-8 times less than steam ones.

    The process of generating electricity at TPPs can be divided into three cycles: chemical - the combustion process, as a result of which heat is transferred to the steam; mechanical - the thermal energy of the steam is converted into rotational energy; electrical - mechanical energy is converted into electrical energy.

    The overall efficiency of a TPP consists of the product of the efficiency (η) cycles:

    The efficiency of an ideal mechanical cycle is determined by the so-called Carnot cycle:

    where T 1 and T 2 are the temperature of the steam at the inlet and outlet of the steam turbine.

    At modern TPPs, T 1 = 550 ° C (823 ° K), T 2 = 23 ° C (296 ° K).

    Practically taking into account losses η thermoelectric power plant = 36-39%. Due to the more complete use of thermal energy, the efficiency of the CHPP = 60-65%.

    A nuclear power plant differs from a thermal power plant in that the boiler is replaced by a nuclear reactor. The heat of a nuclear reaction is used to generate steam.

    The primary energy at a nuclear power plant is internal nuclear energy, which, during nuclear fission, is released in the form of colossal kinetic energy, which, in turn, is converted into thermal energy. The installation where these transformations take place is called a reactor.

    A coolant passes through the reactor core, which serves to remove heat (water, inert gases, etc.). The coolant carries heat into the steam generator, giving it to the water. The resulting water vapor enters the turbine. The reactor power is controlled using special rods. They are introduced into the core and change the neutron flux, and hence the intensity of the nuclear reaction.

    The natural nuclear fuel of a nuclear power plant is uranium. For biological protection against radiation, a layer of concrete several meters thick is used.

    When 1 kg of coal is burned, 8 kWh of electricity can be obtained, and when 1 kg of nuclear fuel is consumed, 23 million kWh of electricity are generated.

    For more than 2000 years, mankind has been using the water energy of the Earth. Now the energy of water is used in hydropower plants (HPP) of three types:

    • hydraulic power plants (HPP);
    • tidal power plants (TPS), using the energy of the ebb and flow of the seas and oceans;
    • pumped storage stations (PSPP), accumulating and using the energy of reservoirs and lakes.

    Hydropower resources in the turbine of the power plant are converted into mechanical energy, which is converted into electrical energy in the generator.

    Thus, the main sources of energy are solid fuel, oil, gas, water, energy of decay of uranium nuclei and other radioactive substances.

    

    The process of converting thermal energy into electrical energy is reflected in simplified (principal) or complete thermal diagrams.

    Basic thermal diagram of TPP shows the main flows of heat carriers associated with the main and auxiliary equipment in the processes of converting the heat of combusted fuel for the generation and supply of electricity and heat to consumers. In practice, the basic thermal diagram is reduced to the diagram of the steam-water duct of a TPP (power unit), the elements of which are usually represented in conventional images.

    A simplified (principal) thermal diagram of a coal-fired heat power plant is shown in Fig. 3.1.

    Coal is fed to the fuel bunker 1 , and from there to the crushing plant 2 where it turns to dust. Coal dust enters the furnace of the steam generator (steam boiler) 3 , which has a system of pipes in which chemically purified water, called nutritional water, circulates. There is water in the boiler

    Rice. 3.1. Simplified thermal diagram of a steam turbine

    a pulverized coal power plant and the appearance of a steam turbine wheel

    heats up, evaporates, and the resulting saturated steam is brought in a superheater to a temperature of 400-650 ° C and under a pressure of 3 ... 25 MPa is fed through a steam line to a steam turbine 4 ... Superheated steam parameters T 0 , P 0 (temperature and pressure at the turbine inlet) depend on the power of the units. At the IES, all steam is used to generate electricity. At a CHP plant, one part of the steam is completely used in the turbine to generate electricity in the generator 5 and then enters the condenser 6 , and the other, having a higher temperature and pressure, is taken from the intermediate stage of the turbine and is used for heat supply (in Fig. 3.1, the dashed line). Condensate pump 7 through the deaerator 8 and then with a feed pump 9 fed to the steam generator. The amount of extracted steam depends on the needs of enterprises in heat energy.

    Complete Thermal Diagram (PTS) differs from the fundamental one in that it completely displays equipment, pipelines, shut-off, control and protective valves. The complete thermal diagram of the power unit consists of diagrams of individual units, including the general station unit (tanks of reserve condensate with transfer pumps, replenishment of the heating network, heating of raw water, etc.). Auxiliary pipelines include bypass, drainage, drain, auxiliary, steam-air mixture suction pipelines. The designations of the lines and fittings of the PTS are as follows:

    3.1.1.1. Thermal diagrams of the ces

    Most of the IESs in our country use coal dust as fuel. To generate 1 kW ∙ h of electricity, several hundred grams of coal are consumed. In a steam boiler, more than 90% of the energy released by the fuel is transferred to steam. In a turbine, the kinetic energy of the steam jets is transferred to the rotor (see Fig. 3.1). The turbine shaft is rigidly connected to the generator shaft. Modern steam turbines for thermal power plants are high-speed (3000 rpm) highly efficient machines with a long service life.

    HPPs of large capacity on fossil fuel are currently being built mainly for high initial steam parameters and low final pressure (deep vacuum). This makes it possible to reduce the heat consumption per unit of generated electricity, since the higher the initial parameters P 0 and T 0 before the turbine and below the final steam pressure P to, the higher the efficiency of the installation. Therefore, the steam entering the turbine is brought to high parameters: temperature - up to 650 ° С and pressure - up to 25 MPa.

    Figure 3.2 shows typical simplified thermal schemes for fossil fuel power plants. According to the scheme in Figure 3.2, a heat is supplied to the cycle only when steam is generated and heated to the selected superheat temperature t lane; according to the scheme in Figure 3.2, b Along with the transfer of heat under these conditions, heat is supplied to the steam after it has worked out in the high-pressure part of the turbine.

    The first circuit is called a circuit without reheating, the second is called a circuit with reheating of steam... As is known from the course of thermodynamics, the thermal efficiency of the second scheme with the same initial and final parameters and the correct choice of reheat parameters is higher.

    For both schemes, steam from a steam boiler 1 goes to the turbine 2 located on the same shaft with an electric generator 3 ... Exhaust steam is condensed in the condenser 4 cooled by service water circulating in the tubes. Turbine condensate by condensate pump 5 via regenerative heaters 6 fed into the deaerator 8 .

    The deaerator serves to remove gases dissolved in it from water; at the same time in it, as in regenerative heaters, the feed water is heated by steam taken from the turbine extraction. Deaeration of water is carried out in order to bring the content of oxygen and carbon dioxide in it to permissible values ​​and thereby reduce the rate of metal corrosion in the water and steam tracts. At the same time, the deaerator may be absent in a number of thermal schemes of the IES. In this so-called neutral-oxygen water regime, a certain amount of oxygen, hydrogen peroxide or air is supplied to the feed water; In this case, a deaerator is not needed in the circuit.

    R
    is. 3.1. Typical thermal schemes for steam turbine

    fossil-fired condensing units without

    intermediate superheating of steam ( a) and with an intermediate

    overheating ( b)

    Deaerated water with a feed pump 9 through heaters 10 supplied to the boiler plant. Heating steam condensate formed in heaters 10 , cascades into the deaerator 8 , and the condensate of the heating steam of heaters 6 is supplied by a drain pump 7 into the line through which the condensate flows from the condenser 4 .

    The described thermal schemes are to a large extent typical and change insignificantly with an increase in the unit power and initial steam parameters.

    The deaerator and feed pump divide the regenerative heating circuit into HPH (high pressure heater) and LPH (low pressure heater) groups. The LDPE group, as a rule, consists of 2–3 heaters with cascade drainage up to the deaerator. The deaerator is fed with steam of the same extraction as the upstream HPH. Such a scheme for switching on a deaerator for steam is widespread. Since a constant steam pressure is maintained in the deaerator, and the pressure in the take-off decreases in proportion to the decrease in the steam flow to the turbine, such a scheme creates a pressure reserve for the take-off, which is implemented in the upstream HPH. HDPE group consists of 3-5 regenerative and 2-3 auxiliary heaters. In the presence of an evaporative installation (cooling tower), the evaporator condenser is connected between the LPH.

    IES producing only electricity have a low efficiency (30 - 40%), since a large amount of generated heat is discharged into the atmosphere through steam condensers, cooling towers, and is lost with flue gases and condenser cooling water.